Air Cooled Chiller Unit | Chiller Unit

Air Cooled Chiller Unit | CHPAW HANBELL

Quote inquiry

Air Cooled Chiller Unit

Specification Table [Air Cooled Chiller Unit]

HANBELL screw comp.

Model. Model PAW 400WHH PAW 500WHH PAW 600WHH PAW 800WHH PAW 1000WHH
호칭출력 40HP (30KW) 50HP (37KW) 60HP (45KW) 80HP (60KW) 100HP (75KW)
법정냉동능력 19.41 RT 24.35 RT 27.41 RT 36.35 RT 45.17 RT
Power Supply Main 3PH 220V/380V 60Hz
Control 1PH 220V 60Hz
Used refrigerant R-22
Refrigeration ability (Kcal/h) ET ℃ ※ CT : 50 ℃ +5℃ 121090 154890 174670 231430 296790
+2℃ 108600 138940 156650 207580 266190
0℃ 100280 128310 144650 191690 245790
-5℃ 82390 105440 118940 157550 202010
-10℃ 67250 86090 97090 128570 164950
Comp. Model RC2-140B RC2-170B RC2-200B RC2-260B RC2-320B
Starting Y - Δ
Start current 610 / 370 740 / 445 850 / 490 1315 / 830 1700 / 930
Max. Operating current 172 / 100 218 / 126 240 / 139 320 / 185 390 / 226
Discharge rate 165 207 233 309 384
oil type Suniso 4GS
Volume 7 ℓ 7 ℓ 8 ℓ 14 ℓ 16 ℓ
apa. Control Stepless 33 ~ 100 % 25 ~ 100 %
Step 33, 66, 100 % 25 , 50 , 75 , 100 %
Evpa. Heat exchanger type Shell & Tube type
Water temp.(℃) Inlet 12℃ / Outlet 7℃
Water flow rate (㎥/h) 21.72 27.788 31.33 41.516 53.238
Cond. Heat exchanger type Fin & Tube
Condenser model PAW 500 PAW 600 PAW 700 PAW 1000 PAW 1200
Fan Fan dia(Φ x EA) 630 x 4 630 x 6 630 x 6 630 x 8 630 x 12
Power(KW x EA) 0.75 x 4 0.75 x 6 0.75 x 6 0.75 x 8 0.75 x 12
Air volume(CMM) 760 1140 1140 1520 2280
Condenser pressure control High Pressure Switch
Protections High, Low Pressure Switch, Reverse Phase Relay, Motor internal thermostat, Safety valve
Components Receiver, Filter Drier, Sight Glass, Liquid Pipe Valve, Pressure gauge, Solenoid Velve
Connection (A) 80 100 100 125 125
External Dimension L 1976 1976 1976 1976 1976
W 1860 2580 2580 3400 4840
H 1948 1948 1948 1948 1948
Anchor Dimension ( L` x W` ) 1918 x 1560 1918 x 2280 1918 x 2280 1918 x 3100 1918 x 4540

◆ Ambient temperature conditions : 35℃ DB (Air Cooled Chiller Unit)

◆ The above specifications are based on cold water pollution coefficient of 0.0001 ㎡ ℃ / kcal

◆ Please refer to electrical characteristics and wiring capacity chart for electrical wiring capacity.

◆ The safety valve (operating at 2.92 MPa) applies only to compressors over 50HP.

※ Specification and photos should be changed without any notice for improvement. (Air Cooled Chiller Unit)